Input Power: AC: 105-135 V or 210-270 V, 50/60 Hz, 5 W DC: 8 -30 VDC @ 0.25 A, exclusive of load (without using optical isolation, an external power supply is needed only for PNP outputs)
Operating Temperature: -10 F to +130 F (-2 C to +55 C) Position Transducer: AVG Automation's RL100, E7R, E8R, or RL101 single-turn resolvers. Maximum Cable Length between Resolver and DMS: 2500 ft (762 m), shielded twisted-pair
Output Format and Resolution: BCD: 360, 1000, or 3600 counts-per-turn Natural Binary: 1000, 1024, 3600 or 4096 counts-per-turn Gray code: 256, 360, 512, 1000, 1024, 3600, or 4096 counts-per-turn
Resolver shaft speed: 3600 RPM (max.) Resolver-to-digital decoder tracking speed: 1800 RPM Display: 3 or 4 digits, 0.25" (6.35 mm) LEDs PLC Sync. Input: (option)
Positive-edge: (LOW to HIGH) and Negative-edge: (HIGH to LOW) triggered. (See Input Logic for Voltage and Current specification: )
PC-handshake strobe: 30 s minimum width
Strobe Delay to Latch Data: 100 s
Transparent Mode/Microfreeze (Standard): |
Output data is continuously updated at full speed. The data is latched for 100 10 s within 30 s of a transition (HIGH to LOW or LOW to HIGH) at data transfer input.
Optical Isolation (Optional): 2500 Volts, on all I/Os except resolver
Input Logic (Channel Select, PLC Sync; Gear Select):
28 VDC Max:
P-type: Logic FALSE: 0 to 0.8 V @ 4 mA; Logic TRUE: 2.4 V @ 3.2 mA
N-type: Logic FALSE: 3.8 V @ 0.4 mA; Logic TRUE: 0 to 0.8 V @ 3.2 mA
C-type: Logic FALSE: 0 to 0.8 V @ 3.2 mA; Logic TRUE: 3.8 V @ 0.4 mA
0 to 5 VDC Logic:
T-type: Logic FALSE: 0 to 0.8 V @ 3.2mA; Logic TRUE: 2.4 V @ 0.4 mA Channel Select Timing: Input Multiplexing: 100 ms from channel select Output Multiplexing: 15 s from channel select Gear Select Timing: 15 s from gear ratio select input |